iSMA-B-MIX38
About the product
One of the most easy to setup and most flexible IO Modules on the market. This module provides the best value per point with the lowest footprint and will make you deliver any BMS project on time and budget. The module has 8 Universal Inputs, 12 Digital Inputs, 6 Analog Outputs, 12 Digital Outputs and is ideal for larger projects.
This module is fully compatible with any Modbus or Bacnet system including the following: Tridium Jace3, Jace6, Jace8000 Compatible, Trend IQ3, IQ4 Bacnet IP Compatible, Siemens PX range, Cylon Bacnet controllers, Schneider Electric StruxureWare Bacnet controllers, OSS NeOSS building management controller, Priva Blue ID, Distech EC Bos, DELL EDGE GATEWAY 5000, Compatible with any Honeywell Centraline Hawk, Delta Controls Compatible IO Modules
Inputs & Outputs
8xUniversal Inputs (8UI)All universal inputs have 16-bit resolution which support the following types of inputs:
- Temperature input support the following types of sensors: 10K3A1, 10K4A1, Carel 10K, 20K6A1, 2.2K3A1, 3K3A1, 30K6A1, SIE1, TAC1, SAT1, Pt1000, Ni1000
- For sensor Pt1000 and Ni1000 use only 16bit resolution
- Voltage input 0-10VDC: input resistance 100kΩ accuracy ±0,1% measurement resolution 3mV@12bit and 1mV@16bit
- Current input 0-20mA - Required external resistor: 200 Ω, sold separately
- Resistive input 0-1000kΩ: measurement resolution for 20kΩ load 20Ω@12bit and 1Ω@16bit
- Dry contact input
- Dry contact inputs
- Fast pulse counter up to 100 Hz
All analog outputs are equipped with 12-bit ADC provides10 mV resolution and accuracy less than ±0,5%. They support the following output types:
- Output 0-10V DC maximum load up to 20mA
- PWM: 0,01Hz, 0,1Hz, 1Hz, 10Hz, 100Hz
- Relay output (NO) max. 3A, 250 VAC/30 VDC
- Cortex-M3
- Interface RS485 half duplex
- Up to 99 devices on the bus
- Protocols: MODBUS or BACnet
- Baud rate: 2400 to 115200 bps
- 24V AC/DC
- Dimension: 160x110x62 mm.
- Construction: plastic, self-extinguishing (PC/ABS)
- DIN rail mounting (DIN EN 50022 norm)
- Cooling: internal air circulation
- Operating temperature: -10°C to 50°C
- Storage temperature: -40°C to 85°C
- Relative humidity: 5 to 95%, no condensation
- Ingress Protection Rating: IP40 – for indoor installation
Do you have a question about this product?
 
In the DOWNLOAD session you can find:
The ISMA driver for Niagara, which contains the ISMA device Palette
ISMA configurator which is needed for updating firmware and configure modules
For any help please contact our support here
Delivery times
For uk clients we deliver all goods ordered by 14:00 in the next working day.